Sterling QVEF User Manual Page 10

  • Download
  • Add to my manuals
  • Print
  • Page
    / 28
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 9
VENTING FOR POWER VENTED (CATEGORY III) UNIT HEATERS
The venting system for these appliances shall terminate
at least four feet (1.2m) below, four feet (1.2m) horizontal
from, or one foot (0.3m) above any door, window, or
gravity air inlet into any building.
Through the wall vents for these appliances shall NOT
terminate over public walkways, or over an area where
condensate or vapor could create a nuisance or hazard
or could be detrimental to the operation of regulators,
relief valves, or other equipment.
The vent pipe equivalent length must be 5 ft. (1.5m)
minimum and must not exceed 50 ft. (15.2m). Equivalent
length is the total length of straight sections PLUS 15 ft.
(4.6m) for each 90 degree elbow, 8 ft. (2.4m) for each 45
degree elbow, and 10 ft. (3.0m) for the vent cap.
Maintain 6 in. (152mm) between vent pipe and combus-
tible materials. A minimum of 12 in. (305mm) of straight
pipe is required from the venter outlet before installing
an elbow in the vent system. An elbow should never
be attached directly to the venter!
Figure 6 - Horizontal Left Vent Position
(Rear View of Unit Heater)
Figure 7 - Horizontal Right Vent Position
(Rear View of Unit Heater)
Figure 8 - Vertical Vent Position
(Side View of Unit Heater)
10
All unit heaters must be vented! All venting installations
shall be in accordance with the latest edition of Part 7,
venting of Equipment of the National Fuel Gas Code,
ANSI Z223.1, or applicable provisions of local building
codes for natural or power vented units.
Power vented units are designed to be used with
single wall vent pipe utilizing horizontal or vertical
venting arrangements (see Figures 6, 7 and 8). These
arrangements may terminate external to the building
using either a single wall or double wall (Type B) vent.
See Figures 6 thru 10 for special installation requirements
regarding these venting conditions.
CARBON MONOXIDE!
Your venting system must not be blocked by
any snow, snow drifts, or any foreign matter.
Inspect your venting system to ensure adequate
ventilation exists at all times! Failure to heed
these warnings could result in Carbon Monoxide
Poisoning (symptoms include grogginess,
lethargy, inappropriate tiredness, or flu-like
symptoms).
Do not use a type B (double wall)
vent internally within the building on our power
vented units!
If double wall venting is used, components which
are UL Listed and approved for Category III positive
pressure venting systems MUST be used.
A Briedart Type L, Field Starkap or an equivalent
vent cap must be supplied by the customer for each
power vented unit. The vent pipe diameter MUST be as
specifi ed in Table 1 (“D” Dia. Flue Opening). A reducer
must be field installed for 100 through 175 MBH Unit
Sizes. All 300 through 400 MBH Unit sizes are factory
equipped with the required flue increaser. Refer to
Figures 9 through 10D for additional requirements.
Vent Systems - Termination Clearance Requirements*
Minimum Clearances for
Structure Termination Locations
4 feet below
Door, window or any gravity air inlet 4 feet horizontally
1 foot above
Forced air inlet within 10 ft. 3 feet above
Adjoining building or parapet 6 feet
Adjacent public walkways 7 feet above grade
* If the vent terminal is to be installed near ground level, the vent
terminal must be positioned at least twelve inches above the maximum
anticipated snow depth (see page 11 for Canadian requirements).
Power Venter
Tee With Drip Leg &
Cleanout Cap At Lowest
Point Of Vent System (Typ.)
D4073
To Horizontal Flue
Vent Termination
Reducer/Increaser
Where Applicable
D4071
AIR FLOW
Power Venter
Tee With
Drip Leg &
Cleanout Cap
To Vertical Flue
Vent Termination
Reducer/Increaser
Where Applicable
Page view 9
1 2 ... 5 6 7 8 9 10 11 12 13 14 15 ... 27 28

Comments to this Manuals

No comments