AIK-IOM-1J30-09444X9 Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read this suppl
2VENTING FOR POWER VENTED DUCT FURNACES (CATEGORY III) GENERAL GUIDELINESAll duct furnaces must be vented! All venting installations shall be in acco
3VENTING FOR POWER VENTED DUCT FURNACES (CATEGORY III) GENERAL GUIDELINES (CONTINUED)ADDITIONAL REQUIREMENTS FOR CANADIAN INSTALLATIONSREFER TO SPECIF
4INSTALLATION INSTRUCTIONSAIR INLET COLLARRemove screen and mounting plate from air inlet on top panel of unit by removing 4 screws. Secure inlet col
58. Each slip joint must be secured with at least three corrosion resistant screws. Two full turns of 3M #425 Aluminum Foil Tape or its equivalent mu
6Figure 3a – Vertical Inlet/Vent Locations, Separated CombustionFigure 3b – Horizontal Inlet/Vent Locations, Separated Combustion VENTING FOR SEPARA
7Figure 4a – Vertical Arrangement, Single Wall Vent System to Single Wall Termination Figure 4b – Horizontal Arrangement, Single Wall Vent System to S
8Figure 5a – Vertical Arrangement, Single Wall Vent System to Double Wall Termination Figure 5b – Horizontal Arrangement, Single Wall Vent System to D